Present: P. Collet, M. De Saegher, J. Lehrbach, A. Martinez Selles, L. Roy, H. Schindler, A. Tauro, B. Vindevogel

Civil engineering (SMB)

  • ALICE planning revision end of this week.
  • ALICE drawings will be sent around this Friday.
  • LHCb drawings (first version for technical specifications) expected for next week. Tender documents are in preparation (ready next Friday). 

FAT in Madrid

  • Water consumption was much higher (up to a factor four) than estimated. Does this have any implication on the installation (e. g. sizing of water pipes)? Automation to re-check numbers with Stulz.
  • Automation to summarise FAT results in an official document.
  • Why was the inside humidity not stable? Automation to ask Stulz.
  • First hour of the test at 38° C outside air temperature was not recorded. 
  • Temperature window around the set point was +/- 1.5° C instead of +/- 0.5° C.
    Johannes asked whether a temperature window of +1/-2° C could be agreed on.

Module FAT in Belgium

  • Johannes to check ALICE availability in week 30.
  • Johannes requests the test of the ALICE IT module to be done with the maximum load (528 kW) and that a test with Delta T = 10° C be included.
  • Resistance of earthing system of the container to be defined with a reasonable number for the FAT, e. g. 0.5 Ohm.

Power cables

  • Automation to send specifications. ALICE/LHCb to check lead time if the cables are ordered via the CERN store.

A. O. B.

  • The first ALICE module is scheduled to arrive at Automation on Monday.

Next meeting: 22 May, 10.15

 

There are minutes attached to this event. Show them.
    • 10:15 10:35
      Updates from CERN 20m
      • Open questions from CyberHandler FAT 10m
        • Humidity
          What caused the increase in the inside air humidity at 38° C conditions? What stopped the increase? Is the humidity directly connected to the outside humidity?
        • Water consumption
        • Data of the first hour of the test at 38°C (9:30-10:30).
        • What is a realistic temperature window around the set point?
        • Stability test at 16° C?


         

    • 10:35 10:55
      Updates from Automation 20m
      Speakers: Mr Bart Vindevogel (Automation NV), Patrick Collet (Automation NV)