Schedule (technical): Mentions power supply exchange to increase number of spares. 1h to be scheduled once EPC confirms readiness (before holidays season). Possibly on the 1st of July ?
From Julien:
YHRS.QP550-NEG and YHRS.QP550-POS model from 1250V NEG /POS to 2000V NEG / POS, because I have a lot of 2000V module in spare.
To be able to swap 1250V model with 2000V model a PLC update must be done. If you are agree with this modification. I will make a request to my colleagues from EPC control. They will prepare a new version of PLC software and we will wait for your green light, once the intervention will by scheduled. I would recommend to not wait to many weeks due to summer holidays.
To be clear, this modification will just change the maximum voltage rating of YHRS.QP550-NEG and YHRS.QP550-POS, and I not expecting to generate any other control issue as it is from my point of view, a minor change.
The complete intervention should take one hour and during that time the power converters listed in the attached file will be OFF.