Participants: A.Lechner, B.Salvachua, P.A.Thonet, D.Mirarchi, R.Bruce, S.Morales, P.Schwarz
- BLM dumps during Run 3 due to off-momentum losses in IR3 at the start of the ramp
- Could be a performance limitation for HL-LHC
- Aim to increase thresholds by a factor of 2-3 -> power loss of around 200kW
- Need to understand how much power loss can be allowed in IR3
- Power loss over a certain period
- Different thresholds for different time durations
- Non-negligible fraction of the power loss goes to the warm magnets
- Relative power deposition higher in the warm magnets in IR3 with respect to IR7 due to different layout (from simulations)
- At injection energy, most loaded MB in IR3 would receive ~12% of the power deposition
- 24kW if we allow for 200kW in IR3
- Power deposition limits date back from Run 1
- 49kW max allowed power deposition in a single MQW
- Nominal current from Run 1, not updated
- Now we could allow less at top energy
- Idea to update these assumptions
- Magnet running at less than 60 degrees C
- Water flow ok for MQW
- Same exercise can be done for MBW
- Add present current for operation of the two magnets
- Is it lower at injection? Can we have more margin then?
- Magnets cooled in parallel
- Possibility to increase the water flow locally for specific magnets
- Action: More detailed profile to see how power is deposited in MBW. Which part goes to the yoke and which part to the coil.
- Action: Confirmation that the assumptions shown by Anton are still up to date. Repeat calculations for MBW and MQW.
- Action: Check possibility to increase water flow locally for specific magnets.
- Action: Check magnet current at injection.
- Action: Collection of steady-state losses during Run 3
- HL-LHC specifications 1MW for 10s
- Worries about expected power deposition in IR7 with HL-LHC expected maximum allowed loss rate of 1MW
- Possibility to log temperature on the most critical magnets
- Stickers on magnets to see the maximum temperature achieved on magnets
- They should be radiation-hard
- Measure from power converters the voltages during operation or quench test
- We hit the yoke of the magnets, but not directly in contact to the coils
There are minutes attached to this event.
Show them.