Presentation from Joel and Franck
status:
- system underperforming: 2 degrees variation during a day
- lack of monitoring: only the temperature is available
- difficult to know what the system is doing
- no monitoring of the fan status, pressure/flow, setting of the valve opening
- poor remote cotrollability: only set temperature and door opening limits
- lack of insulation for the doors
- poor/degraded air tightness
proposed improvements:
- better insulation:
- doors'insulation
- air thightening foam replacement
- adding extra monitoring:
- better temperature probes
- valve setting
- input and output flow
- fan rotation speed
- adding extra controls:
- fan switch
- PID remote retraining
- remote valve control
- status dashboard
proposed plan of action:
- cleaning of the heat exchanger in one point this YETS
- cleaning of all heat exchangers in LS3
- replacement in one point of the heat exchangers with a spare set
- cleaning of the removed exchangers to become the new spares
- repeat from start in another point
- installation of a prototype system in this YETS
- system to be place in parallel at first and 'passive'
- the test system will be overequipped (superset of the monitoring)
- switch to the new system after validation of the integration
- definition of which sensors are relevant after few months of experience
- installation of the new systems in LS3
Presentation from Enrique
- ICS offers a full service for systems using PLC:
- development
- support for the system definition
- maintenance and piquet
- the proposed solution is fully integrated in the control system
- for our systems they suggest a PLC per point
- cost per point including all the sensor interfaces: 2kCHF
- the sensors wiring is up to BI
- the sensors are to be provided by BI
- the development of the control SW is a 1 tantum of 62k including the suppoort and maintenance after
Discussion and actions:
- the intervention is estimated to 4 hours per rack but with large uncertainties (better estimate after YETS)
- replacement and cleaning of the exchanger
- cabling of sensors
- insulation
- the cost per rack for sensors and insulation is estimated at less than 1k per rack
- flowmeter and valves to be rediscussed with EN/CV <= action on Franck and Joel
- the total cost per BA is estimated to ~8k: total material cost 64k
- with the development cost, originally assumed on BI, we arrive to 130k
There are minutes attached to this event.
Show them.