102nd BLM Thresholds Meeting (pp-ref run and proton quench test)

Europe/Zurich
774/1-079 (CERN)

774/1-079

CERN

20
Show room on map
Anton Lechner (CERN), Belen Maria Salvachua Ferrando (CERN), Sara Morales Vigo
Zoom Meeting ID
67029942609
Host
Belen Maria Salvachua Ferrando
Useful links
Join via phone
Zoom URL

Participants: D.Wollman, B.Salvachua, A.Lechner, C.Hernalsteens, C.E.Montanari, P.Hermes, N.Triantafyllou, F.Carra, S.Redaelli, R.Bruce

 

Belen first presentation:

Two corrections: luminosity in colliding IRs and IR7 from collimation

  • pp reference run needs correction in thresholds for different energy and luminosity
    • To avoid 30% warning level in collisions
    • Anton compares that the higher factor needed in LHCb is because there is no TAS
    • Comments that ATLAS might have a higher luminosity in the end, maybe have as target luminosity 3e33
      • Belen will check with Reyes
      • Maybe give some margin also to IR8 in case of noise
      •  
    • Energy level 11 
      • Check also energy level 10
  • Triplets IR8 
    • Implement only in the energy level in the master thresholds the correction to RS08 
      • More simple corrections to have safer changes
  • IP8 TCTs 
    • Same approach, but fixing to RS10
  • IP1 and IP5 
    • Possibility also of doing by MF, but preferred to do change in master threshold to keep it homogeneous
  • For scaling in IP7:
    • Allowing 300kW with MF=0.6
    • Scaling from second set of loss maps
    • Proposal -> changing only monitors that require a factor higher than 1.3 -> limiting at 250kW instead of 300kW
    • Check the TCT that seems to be limiting from collimation losses after applying collision debris correction

As this is done on only one energy level, it would affect only a small part in the ramp

Implement changes during the technical stop

 

C.E.Montanari presentation:

 

Loss maps 8.5 sigmas in secondaries (relaxed settings)

In B1H strong losses in IR6 too (will we quench first in IR6?)

In B1V comparable cleaning and inefficiency in the DS of IR7, but lower losses in IR6 

Still considering nominal settings for the quench test...

Rescaling to 1.2MW to have margin

In terms of BLM signals in does not change a lot if B1H or B1V

 

F.Carra presentation:

 

Considerations taken into account for the 2013 quench test

Maybe expect to reach 50C during the 2024 quench test...

Do not advise to increase temperature thresholds 

 

Second presentation Belen:

  • Allow 1200kW for bLMs with high response
  • Allow 3600kw for BLMs with low response
  • MF unchanged
  • Proposal to mask two BLMs that are monitoring losses for the other beam
    • In the database
  • Create dedicated families, and move BLMs to them
  • In the DS, signals very low, some of them increased anyway

 

B1V selected!!!

  • Safe approach
  • Similar leakage to the DS wrt B1H

 

There are minutes attached to this event. Show them.