CLIC Module Working Group

→ Europe/Zurich
864/1-C02 - indisponible a partir du 24/04/2017 (CERN)

864/1-C02 - indisponible a partir du 24/04/2017

CERN

50
Show room on map
    • 09:00 → 09:10
      Review of actions 10m
    • 09:10 → 09:30
      TBM Lab: Measurements of air speed and heaters 20m
      Speakers: Eleni Daskalaki (National Technical Univ. of Athens (GR)), Serge Lebet
      Slides
    • 09:30 → 09:50
      TBM CLEX: working temperature and water station 20m
      Speaker: Wilfrid Farabolini (CEA/IRFU,Centre d'etude de Saclay Gif-sur-Yvette (FR))
      Dear colleagues,
       
      Regarding the CLIC module installation, I would like to rise an issue that we could maybe discuss during our next CLIC Module Working Group Meeting: the operational temperature of the CLIC module.
       
      Presently inside CLEX the thermalized water temperature is set around 30 0C with an accuracy of +/- 0.05 0C. This water temperature is the same for all the RF systems (LIL accelerating  structures, PETS and ACS) excepted for the gun that has its own thermal station.
       
      The CLIC module is said to have its operational point at 25 0C (why this difference with the PETS and the ACS installed in TBTS ?).
      If confirmed the CLIC module should have its own water station and cannot be connected to the existing thermal water in CLEX. This solution will also allow more flexibility during the operations.
       
      Now comes the issue of the selection of the water station. For tests in the workshop the nominal thermal load is applied on the module using heaters, this implies a water station with high cooling capabilities. Conversely in CLEX the Drive Beam repetition rate will never be greater than 5 Hz and probably will stay at 0.8 Hz (to be compared to  50 Hz for CLIC).
       
      Consequently, not only the water station could have much lower cooling capabilities but it must be fitted with heating capabilities, that is not presently the case. In effect the module will not reach its RF tuning point (25 oC) in an ambient air temperature of 20 oC in CLEX without heating it using the water circuit.
       
      We have to decide soon which solution to be adopted and the dimensions of the water station that impacts on the installation works foreseen in June (the water station could either be installed in the CLEX gallery or directly in the CLEX if too large).
       
      Best regards
       
      Wilfrid
    • 09:50 → 10:10
      TBM in CLEX. Integration of the subsystems equipment in the CTF control infrastructure. Open discussion based on each system requirements. 20m
      Speaker: responsible CLIC System
      Slides
    • 10:10 → 10:30
      AOB 20m