Mon-Af-Po1.23-06 [115]: Winding Design and simulation of a 120kVA/6kV single-phase HTS transformer

23 Sept 2019, 14:30
2h
Level 3 Posters

Level 3 Posters

Poster Presentation Mon-Af-Po1.23 - Transformers

Speaker

Tengyan Wang

Description

Abstract: Based on the finite element method (FEM), a simulation model of a single-phase HTS transformer was established according to a developed HTS transformer, and the simulation results are in good agreement with the experimental data. On this basis, a 120kVA/6kV single-phase HTS transformer was designed, the primary windings were solenoid coils consisted of 8 helically wound layers, and the secondary windings were consisted of 13 double pancakes connected in parallel with 9 layers. The current distribution in windings, magnetic field and stress analysis under rated working condition and in fault were simulated. The results are important to the design of HTS transformer.
Keywords: HTS transformer, wingding, current distribution, magnetic field, stress

Primary authors

Tengyan Wang Wei Pi (North China Electric Power University) Yiran Meng (North China Electric Power University) Shuwen Ma (North China Electric Power University) Ziqiu Liu (North China Electric Power University) Yinshun Wang (North china electric power university) Changtao Kan (North China Electric Power University)